|
|
CHAPTER 7
DIRECT SUPPORT (INTERMEDIATE) MAINTENANCE INSTRUCTIONS
Section I. GENERAL
7-1. Scope
This chapter provides specific instructions for all maintenance functions authorized direct support maintenance personnel
by the maintenance allocation chart (Appendix B). Included are maintenance, troubleshooting and repair instructions.
7-2. Purpose
These maintenance instructions are for use following isolation of a J-SIIDS malfunction to the Capacitance Proximity
Sensor (CPS).
7-3. Periodic Checks and Services
There are no scheduled preventive maintenance procedures required for the CPS.
Section II. TOOLS AND EQUIPMENT
7-4. Standard Tools and Equipment
The CPS can be maintained with standard tools and a voltohmmeter.
7-5. Special Tools and Equipment
No special tools and equipment are required for direct support maintenance of the CPS.
Section III. TROUBLESHOOTING
7-6. Visual Inspection
Before troubleshooting the CPS make a thorough visual inspection. Check sensor cable and PCS for damage and
evidence of failure. Check CPS housing interior for presence of moisture of foreign matter.
7-7. Troubleshooting
If the CPS malfunctions refer to Table 7-1. Find the trouble that most closely corresponds to that encountered, note the
probable cause (s) and perform the corrective action (s) indicated. If the corrective action in Table 7-1 does not correct
the malfunction the trouble is in the circuit board assembly. Figure FO-1, (located in back of manual) PCS schematic
diagram and the preliminary checks given in Chapter 2 will help to identify the trouble.
CAUTION
Do not adjust R29 Sensitivity Adjust. This is a factory adjustment and calibration
procedures are not included in this manual.
Table 7-1. Installed System Troubleshooting
Trouble
Probable cause
Corrective action
Continuous
proximity
and
tamper
No power reaching CPS.
Troubleshoot 20 VDC power line to
alarms.
CPS.
Continuous proximity alarm, tamper
Proximity alarm wiring open.
Troubleshoot alarm wiring.
alarm normal
Continuous tamper alarm, proximity
Tamper alarm wiring open.
Troubleshoot alarm wiring.
alarm normal.
470K line termination resistor not
Check 470K line termination resistor;
installed or open.
install or replace.
Continuous
tamper
alarm,
no
Sensor cable shorted.
Troubleshoot sensor cable
proximity alarm.
Intermittent proximity false alarms.
Poor sensor cable connection to one
Inspect sensor cable equipment
or more item of equipment.
connections; repair as necessary.
Foreign objects touching or near
Inspect around, behind, and under
protected equipment
protected equipment, remove dirt,
paper, wastebaskets, or any other
objects which might disturb the static
7-1
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |