NOTE
Ensure the file selected for downloading is the same as the RADC being downloaded to.
Step 6. Press D. The following appears:
Download to remote
Creating configuration image...Done.
RSE data size
: xxxx
RSE bytes available
: xxxx
>Download ACE configuration to remote? Press "Y", (yes) and Enter.
Download RSE configuration to remote
Continue?>
Step 7. Press "Y" and Enter. The message "Sending RSE" appears. When downloading is complete, press 9 for
Facilities and Q to quit, and Q again to return to the RSE program.
Step 8. Remove power from the laptop computer and disconnect the serial cable from the Stargate PWA diagnostic port
and the computer.
Step 9. Have the operator do a download for the replaced RADC Stargate PWA and check to ensure the correct status
is being sent to the FEP.