TM 5-6350-262-14/5
NAVELEX 0967-466-9050
TO 31S9-4-38-1
Table 7-1. Control Unit Performance Standards - Continued
Control Setting
Step
Test
Performance
No.
Test
Equipment
Procedure
Standard
Equipment
Under Test
e. Adjust dc power supply
a. TS352B meter should drop
VOLTAGE control for
to approximately 0.5
less than 19 V dc
volt as power supply
indication on meter.
output voltage drops to
less than 19 volts.
f. Adjust dc power supply
a. None.
VOLTAGE control for 20 V
dc indication on meter.
Operating mode switch:
g. None.
a. TS352B meter should
TEST/RESET, then
indicate 19 to 21 V
SECURE
dc.
h. Adjust dc power supply
a. TS352B meter should drop
VOLTAGE control for more
to approximately 0.5 volt
than 21 V dc indica-
as power supply out-
tion on meter.
put voltage is increased
to more than 21 V dc.
POWER: OFF
i. Disconnect dc power supply
a. None.
and TS352B test leads.
Install fuse F2.
7
TS352B: R X 100
POWER: ON
a. Connect TS352B test leads
a. Meter should indicate less
(zero meter)
Operating mode
between terminals S-3
than 2000 ohms.
switch: SECURE
and 3R.
b. Remove ac power fuse F1.
a. Meter should indicate more
than 100,000 ohms.
c. Install ac power fuse F1.
a. None.
d. Connect TS352B test leads
a. Meter should indicate more
between terminals S-2
than 100,000 ohms.
and -2R.
Stopwatch
Operating mode switch:
e. None.
a. Meter should indicate less
TEST/RESET, then
than 2000 ohms for 4.5
SECURE
to 6 seconds.
8
TS352B:
POWER: ON
a. Connect TS352B test leads
a. Meter should indicate
+ D.C.
Operating mode
between terminals
0 V dc.
50V
switch: SECURE
A-7(+) and 6(-).
Operating mode switch:
b. Check for approximately 27.5
a. Meter should indicate 26.5
ACCESS
V dc between terminals
to 30 V dc at each
7(+) and 6(-) of ter-
test point.
minal boards A through E.
9
TS352B: R X 100
POWER: ON
a. Connect TS352B test leads
a. Meter should indicate less
(zero meter)
Operating mode switch:
between terminals
than 2000 ohms.
switch: SECURE
S1-I and -IR.
Stopwatch
b. Momentarily disconnect
a. Meter should indicate more
orange jumper wire from
than 100,000 ohms for
terminal F-1.
10 2 seconds.
Operating mode switch:
c. Momentarily disconnect
a. Sonalert should sound
(for 10 :2 seconds).
TEST/RESET
orange jumper wire from
terminal F-1.
Stopwatch
d. Disconnect
a. Sonalert should
sound for 10 2
orange jumper
wire from termi-
seconds after jumper
nal F-1
for 13 wire is reconnected.
seconds then recon-
nect it.
e. Momentarily dis-
a. Sonalert should
connect orange
sound (for 10 2
jumper wire from
seconds).
terminal F3.
7-16