Table 7-1. Control Unit Performance Standards - Continued
Control Setting
Step
Test
Performance
No.
Test
Equipment
Procedure
Standard
Equipment
Under Test
Operating mode switch:
j. None.
a. All alarm LED's should
TEST/RESET, then
go out.
SECURE
b. Alarm LED F should illum-
inate after expiration of
exit time delay.
k. Disconnect orange
a. Alarm LED A
jumper wire at
should not illumi-
terminal 1 of ter-
nate.
minal board A.
l. Connect orange
a. None.
jumper wire at
terminal A-1 and
install orange
jumper wire be-
tween terminals 1,
2, and 3 on ter-
minal board F.
m. Connect TS352B
a. Meter should indi-
negative lead to
cate less than 0.5
ground and posi-
volts at each test
tive lead momen-
point.
tarily to each of
the following test
points:
AlTP1, A2TP1
A2TP2, A3TP1,
A3TP2, A4TP1,
A4TP2, A5TP1,
A5TP2, A6TP1,
A6TP2, A7TP1, and
A7TP2.
5
TS352B:
POWER: ON
a. Connect TS352B
a. None.
+D.C.
Operating mode
negative lead to
50V
switch: TEST/
ground. Connect
RESET
positive lead to
test point A10TP1.
Operating mode
b. None.
a. Meter should indi-
switch: SECURE
cate 19 to 21 V dc.
c. Remove one end of
a. Meter indication
jumper wire con-
should drop to ap-
nected between
proximately 0.5
terminals L2-3 and
volt when jumper
-4.
connection is
broken.
d. Reconnect jumper
a. None.
wire.
6
DC power supply:
POWER: OFF
a. Connect TS352B negative
a. None.
VOLTAGE: 20 V dc
Operating mode switch:
lead to ground. Con-
indication on meter.
TEST/RESET
nect positive lead to
CURRENT: 1A
test point A10TP1.
TS352B:
b. Remove fuse F2.
a. None.
+D.C.
POWER: ON
c. Connect dc power supply
a. None.
50V
negative lead to ground
and positive lead to
TB23.
Operating mode switch:
d. None.
a. TS352B meter should
SECURE
indicate 19 to 21
V dc.
7-15
|