TM 38-400/NAVSUP PUB 572/AFMAN 23-210 MCO 4450.14/DLAM 4145.12
Table 6-5. Characteristics of Extinguishers. (Continued)
Extinguishing agent
Method of
Capaity
Horizontal
Approximate
Hydrostatic
Protection
UL or ULC
operations
range of
time of
test interval
required
classifications
stream
discharge
below 40
F
Stored pressure
1 1/2 to 2 1/2 lb
5-8 ft
8 to 12 sec
5 or 12 yrs
No
2 to 5-B:C
Cartridge &
2 3/4 to 5 1/2 lb
5-20 ft
8 to 20 sec
5 or 12 yrs
No
5 to 10-B:C
stored pressure.
Cartridge &
7 1/2 to 30 lb
5-20 ft
10 to 25 sec
5 or 12 yrs
No
10 to 60-B:C
stored pressure.
Nitrogen cylinder
75 to 350 lb
1545 ft
20 to 105 sec
5 or 12 yrs
No
40 to 240-B:C
or stored pres-
(wheeled).
sure.
Dry Chemical (Po-
Stored pressure
1 to 2 lb
5-8 ft
8 to 10 sec
5 yrs
No
1 to 5-B:C
tassium Bicar-
bonate).
Stored pressure
2 1/4 to 5 lb
5-12A
8 to 10 sec
5 or 12 yrs
No
5 to 20-B:C
Cartridge or
5 1/2 to 10 lbs
5-20 ft
8 to 20 sec
5 or 12 yrs
No
10 to 60-B:C
stored pressure.
Cartridge or
16 to 30 lbs
10-20 ft
8 to 25 sec
5 or 12 yrs
No
40 to 80-B:C
stored pressure.
Nitrogen cylinder
125 to 300
15-45 ft
30 to 60 sec
5 or 12 yrs
No
80 to 320-B:C
or stored pres-
lbs
sure.
(wheeled).
Dry Chemical (Po-
Stored pressure
2 to 2 1/2 lbs
5-8 ft
8 to 10 sec
5 or 12 yrs
No
5 to 10-B:C
tassium Chlo-
ride).
Cartridge or
5 to 10 lbs
5-20 ft
8 to 25 sec
5 or 12 yrs
No
20 to 40-B:C
stored pressure.
Cartridge or
19 1/2 to 30
15-45 ft
8 to 25 sec
5 or 12 yrs
No
60 to 80-B:C
stored pressure.
lbs.
Nitrogen cylinder
50 to 160 lbs
15-45 ft
30 to 60 sec
5 or 12 yrs
No
120 to 160-B:C
or stored pres-
(wheeled).
sure.
Dry Chemical
Stored
1 to 5 lbs
5-12 ft
8 to 10 sec
5 or 12 yrs
No
2 to 10-B:C
(Ammonium
pressure****
Phosphate)**.
Dry Chemical
Stored pressure
2 1/2 to 8 1/2 lbs
5-12 ft
8 to 12 sec
5 or 12 yrs
No
1 to 3-A and 10 to
(Ammonium
or cartridge.
40-B:C
phosphate)**.
Stored pressure
9 to 17 lbs
5-20 ft
10 to 25 sec
5 or 12 yrs
2 to 4-A and 10 to
or cartridge.
60-B:C
Nitrogen cylinder
15-45 ft
30 to 60 sec
5 or 12 yrs
or stored pres-
sure.
* UL and ULC rating ratings as of 27 December 1974.
** Certain pressurized types have special requirements for hydrotesting to comply with regulations of DOT.
***Carbon dioxide extinguishers with metallic horns do not carry a "C' classification.
**** Some small extinguishers containing ammonium phosphate dry chemical do not carry an "A" classification.
6-39. For all areas of storage.
e. Remove and dispose of scrap and waste
All areas of storage space will have the following
systematically.
housekeeping rules enforced:
f: Clean up work areas as soon as work is
a. Provide adequate lighting.
completed. Remove hazardous objects from floor or
b. Keep machines, equipment, and working
ground areas during work.
surfaces clean and orderly.
c. Provide adequate tool storage and maintain that
from containers or unit loads.
storage in neat order.
h. Allow eating only in authorized places.
d. Provide approved waste containers in sufficient
i. Keep offices and rest rooms in orderly condition.
number.
6-12
|