TM 38-400/NAVSUP PUB 572/AFMAN 23-210 MCO 4450.14/DLAM 4145.12
Table 6-5. Characteristics of Extinguishers. (Continued)
Extinguishing
Method of
Capaity
Horizontal range
Approximate
Protection
UL or ULC
agent
operations
of stream
time of
interval
required
classifications
discharge
below 40
F
Dry Chemical
Cartridge &
4 3/4 to 9 lbs
5-20 ft
8 to 10 sec
5 or 12 yrs
No
10 to 20-B:C
(Foam Compat-
stored pressure.
ible)**.
Cartridge &
9 to 27 lbs
5-20 ft
10 to 25 sec
5 or 12 yrs
No
20 to 30-B:C
stored pressure.
Cartridge &
18 to 30 lbs
5-20 ft
10 to 25 sec
5 or 12 yrs
No
40 to 60-B:C
stored pressure.
Nitrogen cylinder
150 to 350
15-45 ft
20 to 150 sec
5 or 12 yrs
No
80 to 240-B:C
& stored pres-
lbs
sure.
(wheeled).
Dry Chemical
Cartridge &
2 1/2 to 5 lbs
5-12 ft
8 to 10 sec
5 or 12 yrs
No
10 to 20-B:C
(Foam Compat-
stored pressure.
ible) (Potassium
Chloride).
Cartridge &
9 1/2 to 20
5-20 ft
8 to 25 sec
5 or 12 yrs
No
40 to 60-B:C
lbs
stored pressure.
Cartridge &
191/2 to 30
5-20 ft
10 to 25 sec
5 or 12 yrs
No
60 to 80-B:C
stored pressure.
lbs.
Nitrogen cylinder
50 lbs
15-45 ft
30 sec
5 or 12 yrs
No
120-B:C
& stored pres-
(wheeled).
sure.
Dry Chemical
Stored pressure
5 to 11 lbs
11-22 ft
13 to 18 secs
12 yrs
No
40 to 80-B:C
(Foam Compat-
ible) (Potassium
Bicarbonate
Urea based).
Stored pressure
17 to 19 lbs
15-30 ft
26 to 30 secs
12 yrs
No
120-B:C
175 lbs
70 ft
62 secs
12 yrs
No
480-B:C
(wheeled).
Bromotrifluorome-
Self expellent
2 1/2 lbs
4-6 ft
8 to 10 secs
12 yrs
No
2-B:C
thane.
Stored pressure
4 1/2 lbs
10 ft
8 to 10 secs
12 yrs
No
5-B:C
Bromochlorodiflu-
Stored pressure
2 to 4 lbs
8-12 ft
8 to 12 secs
12 yrs
No
2 to 5-B:C
oromethane.
5 1/2 to 9 lbs
9-15 ft
8 to 15 secs
12 yrs
No
10-B:C
Foam
Pressurized
21 oz
4-6 ft
24 secs
-
Yes
1-B
Foam
Chemically gen-
1 1/4, 1 1/2
30-40 ft
40 secs
5 yr
Yes
1-A; 2-B
gal
erated expel-
lent.
Chemically gen-
2 1/2 gal
30-40 ft
11/2 min
5 yr
Yes
2-A:4-B to 2-A:6-
B
erated expel-
lent.
Chemically gen-
5 gal
30-40 ft
2 min
5 yr
Yes
4-A:6-B
erated expel-
lent.
Chemically gen-
17 gal
50 ft
3 min
5 yr
Yes
10-A:10-B to 10-
erated expel-
(wheeled).
A:12-B
lent.
Chemically gen-
33 gal
50 ft
3 min
5 yr
Yes
20-A:20-B to 20-
erated expel-
(wheeled).
A:40-B
lent.
Self expellent
2 1/2 to 5 lb
3-8 ft
8 to 30 sec
5 yr
No
1 to 5-B:C
10 to 15 lb
3-8 ft
8 to 30 sec
5 yr
No
2 to 10-B:C
20 lb
3-8 ft
10 to 30 sec
5 yr
No
10-B:C
50 to 100 lb
3-10 ft
10 to 30 sec
5 yr
No
10 to 40-B:C
(wheeled).
Dry Chemical (So-
Stored pressure
1 lb
5-8 ft
8 to 10 sec
5 or 12 yrs
No
1-B:C
dium Bicarbon-
ate).
6-11
|