TM 5-6350-262-14/5
NAVELEX 0967-466-9050
TO 31S9-4-38-1
Table 7.1. Control Unit Performance Standards - Continued
Control Setting
Step
Test
Performance
No.
Test
Equipment
Procedure
Standard
Equipment
Under Test
Operating mode
e. None.
a. Meter indicates
switch: SECURE
less than 2000
ohms for duration
of combined exit
and entrance time
delays (16 to 200
seconds), then in-
indicates more than
100,000 ohms until
reset (step g).
f. Connect orange
a. None.
jumper wire to
terminal A-1.
Operating mode
g. Depress enclosure
a. Meter should indicate
switch: TEST/
tamper switch to
more than 100,000
RESET then
the alarm position
ohms until reset
ACCESS
then return it
(step h).
to the alarm
bypass position.
Operating mode
h. None.
a. Meter should indicate
switch: SECURE
more than
POWER: OFF
100,000 ohms when
power is turned off.
i. Disconnect
a. None.
TS352B test leads.
12
TS352B:
POWER: ON
a. Connect TS352B test leads
a. Meter should indicate the
+D.C.
Operating mode switch:
to terminal L2-1 (+)
5 volt buss voltage.
10 V
SECURE
and -2 (-).
b. Allow sufficient time for
a. Meter should indicate less
exit time delay (8 to
than 1 V dc after expira-
100 seconds) to expire
tion of entrance time
then momentarily disconnect
delay (8 to 100 seconds).
orange jumper wire from
terminal A-1.
Operating mode switch:
a. None.
a. Meter should indicate the
TEST/RESET
5 volt buss voltage.
Operating mode switch:
d. Allow sufficient time for exit
a. Meter should indicate less
ACCESS
time delay (8 to 100
than 1 V dc after expira-
seconds) to expire then
tion of entrance time delay
momentarily disconnect
(8 to 100 seconds).
orange jumper wire
from terminal A-1.
POWER: OFF
e. Remove TS352B test leads.
a. None
13
TS352B:
POWER: OFF
a. Connect TS352B test leads
a. Meter should indicate
R X 100
between S4 and -7.
infinite resistance:
(zero meter)
TS352B:
POWER: OFF
b. Press TRANSMITTER
a. Meter should indicate
RX1
RESYNC switch.
1 ohm or less.
(zero meter)
d. Restore control unit
a. None.
to original con-
figuration. (Refer to
(7)  Connect a jumper wire between terminals 3
cover screws on power supplies serial numbered 0001
and 4 on terminal board L2.
through 0059:
(8)  Perform the following steps to gain access to
(a)
Loosen inboard terminal screw at TB2-4
the power supply access
7-18