Check resistance between lead 14D (pin end) and ground. If multimeter
Step 7.
indicates more than 4 ohms, repair lead 14D between disconnect and
generator ground. Refer to page 2-371. If multimeter indicates 0 to 4
ohms, troubleshoot generator output circuit. Refer to page 2-133. Con-
nect leads 14D to disconnect.
Disconnect leads 14 from neutral position switch. Place red probe in lead
Step 8.
14 (terminal end). Ground black probe. Check voltage in both 14 leads
(terminal ends). Set MASTER and INST switches ON. Press START
switch. If multimeter indicates no voltage in both leads 14, connect leads
14 to neutral position switch and go to step 10. If multimeter indicates
about 24 volts in one lead 14, connect the lead 14 that measures about 24
volts to neutral position switch and go to step 9. Set MASTER and INST
switches OFF.