TM 5-6350-275-24&P
b. Remote Status Monitor (RSM). The RSM monitors and controls Remote Area Data Collectors. The RSM
communicates with the PMC through the 9600 baud modem link. The direct communication line from the RADCs also
allows the RSM to take over control of the RADCs through the automatic/manual switch to the RSM communication
ports, in the event of a PMC failure.
RSM CHARACTERISTICS
Status Display - Same As Primary Monitor Console (PMC)
Up To 8 Remote Status Monitors (RSMs) for Large Primary Monitor Console (LPMC) and Up To 2 Remote Status
Monitors (RSMs) for Small Primary Monitor Console (SPMC)
Switch-Over From Primary Monitor Console (PMC) to Remote Status Monitor (RSM) Manual Or Automatic Without
Data Loss
Identical Hardware and Software to Primary Monitor Console (PMC)
Uninterruptible Power Supply (6 Hour)
Two Modes of Operation
Monitor Only - Displays All Or Selected Portions Of The Data Displayed At Primary Monitor Console (PMC)
Charged Coupled Device (CCD) Mode - Performs All Of The Functions of the Primary Monitor Console (PMC) For
Selected Remote Area Data Collectors
Supports All Primary Monitor Console (PMC) Communications Media RSM CAPABILITIES AND FEATURES
RSM CAPABILITEIS AND FEATURES
Same as Primary Monitor Console above, except the RSM uses the Data Communication Systems to take control of
the RADCs in the event of a Central Processing Unit (CPU) failure.
c. Remote Area Data Collector (RADC). Collects and processes inputs and outputs from sensors and remote terminal
units. Up to 16 Intelligent Access Controllers (IACs) (31 Doors) can be multi-dropped on an RS-485 line (AUX 1) port,
and up to 31 satellite Leda can be multi-dropped on another RS-485 line (AUX 0) port. Lines can be extended 4000 feet
from the RADC location. A port is also provided for the connection of a lap top computer for unit configuration and
diagnostics. Standard Data communications from the RADC to the PMC is provided by the Mod 2, 1200 baud modem
and the Bell 3002 Data Communication circuit. The RADC can perform standalone access and exit control functions.
The RADC carries its own integral power source (12 vdc, 7 amp hr. battery) to maintain system integrity in the event of
loss of primary power.
RADC CHARACTERISTICS
Interior STARGATE 5000:
20 Sensors With Alarm, Tamper, And Self-Test; Expandable
4 Response Devices; Expandable
Distance to Sensors and Response Devices (RDs) 150 Meters
Up to 31 Doors Entry Control Equipment (ECE) (Entry and Exit)
Distance to Door Controllers 4000 Feet
10 Individually Selectable Microphones (Mics)
Intercom
Exterior STARGATE 1000:
32 Sensors With Alarm and Tamper; Expandable
16 Response Devices; Expandable
Distance To Sensors 1000 Meters
Joint-Services Interior Intrusion Detection System (J-SIIDS) Interface
Locally Configured Using A Laptop Personal Computer (PC)
Interfaces To All Primary Monitor Console (PMC) Communications Media
Data Encryption System (DES) Data Authentication System
Uninterruptible Power Supply (6 Hour); Powers Interior Sensors; 12 or 20 volts direct current (vdc)
1-10
|