Click here to make tpub.com your Home Page

Page Title: Table 5-1. Troubleshooting Procedures - Continued
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 5-6350-264-14&P-11
NAVELEX EE 181-AA-OMI-120/E121 C-7359-60-1
T.O. 31S9-2FSS9-1-11
Table 5-1. Troubleshooting Procedures - Continued
Trouble
Probable cause
Corrective Action
c.
Actuate ACKNOWLEDGE then
RESET switch on Status Mon-
itor Module.
d.
If an alarm condition is displayed,
Status Monitor Module is de-
fective.
e.
To remove Status Monitor Mod-
ule, unlock and open Monitor
Cabinet and turn off switch S1
on power supply. Release
swingout rack. Remove screws
that secure status monitor mod-
ule to rack and remove module
through front of rack.
f.
Remove jumper from terminal 4
of input terminal board. Re-
place Status Monitor Module
in swingout rack and secure
with screws. Secure swingout
rack. Turn on switch S1 on
power supply.
g.
If a no alarm condition is dis-
played, Status Monitor Module
is defective.
h.
To remove Data Receiver and
Status Monitor Module, unlock
and open Monitor Cabinet and
turn off switch S1 on power
supply. Release swingout rack.
Remove screws that secure
Status Monitor Module to rack
and remove module through
front of rack. Remove jumper
from terminals 1-I and 1-L of
Status Monitor Module input
terminal board. Install new
Status Monitor Module in swing-
out rack and secure with screws.
Secure swingout rack. Turn on
switch S1 on power supply.
5-5