TM 5-6350-264-14&P-11
NAVELEX EE 181-AA-OMI-120/E121 C-7359-60-1
T.O. 31S9-2FSS9-1-11
Table 5-1. Troubleshooting Procedures - Continued
Trouble
Probable cause
Corrective Action
f.
Remove jumper from terminal 4 of
input terminal board. Replace
Status Monitor Module in swing-
out rack and secure with screws.
Secure swingout rack. Turn on
switch S1 on power supply.
g.
If a no-alarm condition is dis-
played, Status Monitor Module
is defective.
h.
To remove Status Monitor Module,
unlock and open Monitor Cabi-
net and turn off switch S1 on
power supply. Release swing-
out rack. Remove screws that
secure status monitor module to
rack and remove module
through front of rack. Remove
jumper from terminals 1-I and
1-L of SMM input terminal
board. Install new Status Mon-
itor Module in swingout rack
and secure with screws. Secure
swingout rack. Turn on switch
S1 on power supply.
2.
Set Control Unit mode
Defective Status Monitor
a.
Remove Data Receiver and Status
switch to ACCESS.
Module
Monitor Module from one-zone
Status Monitor
Monitor Cabinet. To remove
Module does not re-
Status Monitor Module, unlock
spond to tamper
and open Monitor Cabinet and
condition.
turn off switch S1 on power
supply. Release swingout rack.
Remove screws that secure
status monitor module to rack
and remove module through
front of rack.
b.
Connect jumper between terminals
1-I, 1-L, and 4 of associated
Status Monitor Module input
terminal board. Replace Status
Monitor Module in swingout
rack and secure with screws. Se-
cure swirigout rack. Turn on
switch S1 on power supply.
5-4
|