TM 5-6350-264-14&P-11
NAVELEX EE 181-AA-OMI-120/E121 C-7359-60-1
T.O. 31S9-2FSS9-1-11
Table 2-3. Monitor Cabinet and Status Monitor Module Operating Procedure M-1
NOTE
When assuming responsibility for attending the Monitor Cabinet(s); ensure that all ALARM
(red) lights are extinguished, that all AC POWER (white) lights are on, and that proper
operating mode (ACCESS or SECURE) is indicated on all Status Monitor Modules. Also
verify that all indicator bulbs are operable by momentarily placing each lamp test switch in
the LAMP TEST position. If lights are burned out, request responsible maintenance
personnel to replace bulbs at earliest opportunity.
Indication
Operator response
1. ALARM indicator lights (red) flashing
a. Momentarily place RESET/ACK switch on associated Status Monitor
and audible tone sounding.
Module in the ACK position.
b. If alarm is not generated during a time of prearranged opening or
securing of protected area or system test, direct security personnel to
indicated protected area (NOTE 1).
c.
After security personnel have investigated cause of alarm, momentarily
place RESET/ACK switch in RESET position to extinguish ALARM
indicator lights.
2. MONITOR AC POWER indicator
a. Momentarily place LAMP TEST/ACKNOWLEDGE switch on Monitor
Cabinet Signal Module in ACKNOWLEDGE position.
b. If lights extinguish, inform designated personnel that ac power to Monitor
Cabinet has just been lost (NOTE 2) (NOTE 3).
c.
If lights stay on steady state, ac power has been restored to Monitor
Cabinet.
a. Momentarily place RESET/ACK switch on associated Status Monitor
3. ACCESS indicator lights(amber)
Module in the ACK position.
flashing and audible signal device
sounding.
b. If change to ACCESS is not part of a prearranged opening of protected
area, direct security personnel to indicated protected area.