Table 7-1. Monitor Cabinet Performance Standards
Control settings
Step
Equipment under
No.
Test equipment
test
Test procedure
Performance standard
TS352B (or equivalent:Power Supply S1 in ON a. Connect TS352B positive
a. Meter indicates +20 1
1.
25 V de range
position.
lead on terminal board pin
V dc.
b. AC MON lamps will be
3 and the negative lead on
pin 4 of the signal module.
illuminated continuously.
a. Remove AC input power
a. AC MON lamps will flash
2
N/A
PSS1 in ON position
(longer than 3 seconds).
on and off. Audible alarm
DSI will sound.
b. None.
b. AC MON lamps will go
N/A
Signal Module S1 is
momentarily placed in the
off. Audible alarm DS1 will
ACKNOWLEDGE position.
go off.
c. Reactivate AC input
c. AC MON lamps will flash
N/A
N/A
power.
on and off. Audible alarm
DS1 will sound.
d. None.
d. AC MON lamps will
N/A
Signal Module S1 is
momentarily placed in the
illuminate continuously.
ACKNOWLEDGE position.
Audible alarm DS1 will go
off.
Power Supply S1 in ON a. Place a jumper between
a. Audible Alarm DS1 will
3.
N/A
position.
signal module terminal
sound.
board pin 1 and pin 4.
b. Remove the jumper from
b. Audible Alarm DS1 will
signal module terminal
be silenced.
board pin 1 and pin 4.
7-7
|