TM 38-400/NAVSUP PUB 572/AFMAN 23-210 MCO 4450.14/DLAM 4145.12
e. Above level of roof truss.
When supplies are
(1) When stack heights do not exceed 15
stacked above the horizontal level
of lower roof truss
feet, an 18-inch clearance will be maintained.
members or beams, the horizontal
clearance between
(2) When stack heights exceed 15 feet, a
supplies and structural members
or other installed
36inch clearance will be maintained.
devices will be 18 inches (fig 6-2).
(3) Regardless of their height, stacks in
nonsprinkled buildings will have a 36-inch clearance,
6-51. Clearances.
except that reclaimed metal drums may be stacked
within 14 to 20 inches from metal joists, rafters, beams,
a. General. Clearances between stored materials
and roof trusses in nonsprinkled buildings of all metal
and walls will not be maintained except as follows:
construction and without electrical wiring.
(1) Substandard firewalls (less than 4-hour
d. Light or heating fixtures. Around light or heating
rating) clearance of 24 inches will be maintained (fig 6-
fixtures, an 18-inch clearance will be maintained.
3).
Figure 6-2. Clearance of material from sprinkler heads and trusses.
door except for the portion of the fire door near the
(2) When infestible subsistence items are
aisle.  For this portion of the fire door, a 36-inch
stored in general purpose storage buildings, an 18 inch
clearance will be maintained between stock and the fire
clearance will be maintained.
door (fig 6-6). Where a protective barricade is provided
(3) No
clearance
is
required
when
for the fire door, no clearance between stock and
nonhazardous materials are stored in general purpose
barricade is required.
storage buildings, except a 24-inch clearance around
personnel doors or fire aisles (fig 6-5).
6-52. Aisles.
(4) When materials stored are subject to
Aisles will not be maintained for access to electrical
excessive swelling, clearance usually not exceeding 12-
equipment, fire fighting equipment, or sprinkler valves,
inches (fig 6-6).
except where such equipment or valves cannot
conveniently be moved to a more accessible location.
b. Clearance to maintain nonhazardous materials
storage block limitations. When clearances are found
6-53. Exceptions.
necessary to maintain storage block limitations, such
Exceptions to the requirements may be authorized
clearance between stacks will not be more than 4 feet in
where such exceptions will result in increasing space
width for 2,000-square foot blocks or 6 feet for 8,000-
utilization without materially increasing the fire risk.
square foot blocks.
Requests  for  such  exceptions,  with  adequate
c. Clearance around fire doors.
A 24-inch
clearance will be maintained between stock and the fire
6-18