TM 38-400/NAVSUP PUB 572/AFMAN 23-210 MCO 4450.14/DLAM 4145.12
contain horizontal channels.
Minor quantities of
producing a fire that would cause appreciable damage
to the commodities stored or to noncombustible wall,
commodities  of  hazard  greater  than  ordinary
combustibles may be included without affecting this
floor, or roof construction.
Ordinary combustible
commodities in completely sealed noncombustible
general classification.
containers may qualify in this classification.  General
c. Type III storage.  Type III storage is that in
commodity storage that is subject to frequent changing
which the stored commodities, packaging, and storage
and storage of combustible packaging and storage aids
aids are noncombustible or contain only a small
is excluded from this category.
concentration of combustibles which are incapable of
Section VII. Fire Suppression Equipment (Portable Fire Extinguishers, 29 CFR 1910.157)
6-26. Cabinet mounting.
6-20. Operable condition.
Extinguishers mounted in cabinets or well recesses or
Portable extinguishers will be maintained in a fully
set on shelves will be placed so the extinguisher
charged and operable condition and kept in their
operating instructions face outward.  The location of
designated places at all times when they are not being
such extinguishers will be marked conspicuously.
used.
6-27. Vibrating locations.
6-21. Location.
Extinguishers installed under conditions where they are
Extinguishers will be conspicuously located where they
subject to severe vibration will be installed in brackets
will be readily accessible and immediately available in
specifically designed to cope with this vibration.
the event of fire.  They will be located along normal
paths of travel.
6-28. Temperature range.
6-22. Marking of location.
Extinguishers  will  be  suitable  for  use  within
a
temperature range of at least plus 40F. to 120F.
Extinguishers will not be obstructed or obscured from
view.  In large rooms, and in certain locations where
visual obstruction cannot be completely avoided, means
6-29. Extreme temperature exposure.
will be provided to indicate the location and intended
When extinguishers are installed in locations subjected
use of extinguishers conspicuously.
to temperatures outside the range prescribed in this
subparagraph, they will be of a type approved or listed
6-23. Marking of extinguishers.
for the temperature to which they will be exposed or
placed in an enclosure capable of maintaining the
If extinguishers intended for different classes of fire are
temperature  within  the  range  prescribed  in  this
grouped,  their  intended  use  will  be  marked
subparagraph.
conspicuously  to  ensure  choice  of  the  proper
extinguisher at the time of a fire.
6-30. Selection of extinguishers.
6-24. Mounting of extinguishers.
The selection of extinguishers for a given situation will
depend upon the character of the fires anticipated, the
Extinguishers will be installed on the hangers or in the
construction and occupancy of the individual property,
brackets supplied, mounted in cabinets, or set on
the vehicle or hazard to be protected, ambient
shelves unless the extinguishers are of the wheel type.
temperature conditions, and other factors. The number
of  extinguishers  required  will  be  determined  by
6-25. Height of mounting.
reference to paragraph m below.
Approved fire
Extinguishers having a gross weight not exceeding 40
extinguishers will be used to meet the requirements of
pounds will be installed so that the top of the
this section.
extinguisher is not more than 5 feet above the floor.
Extinguishers having a gross weight greater than 40
pounds (except wheeled types) will be so installed that
NOTE
the top of the extinguisher is not more than 3 1/2 feet
Approved means listed or approved by (1) at
above the floor.
least  one  of  the  following  nationally
recognized testing laboratories:
Factory
Mutual  Engineering  Corporation;  Under
6-6