TM 38-400/NAVSUP PUB 572/AFMAN 23-210 MCO 4450.14/DLAM 4145.12
damaged and no longer capable of performing its
11 Under no circumstances shall
intended purpose.
lithium cells or batteries be handled, placed, or
3 Used batteries shall not be
transported with flammable liquids or gases, or a
significant concentration of flammable fumes.
pierced, crushed, burned, dropped, cannibalized,
dismantled, or carelessly handled, nor shall they be
b. Secondary batteries. Secondary batteries will
short-circuited, charged, or reused. (Reuse does not
never be piled on top of one another, rather, they will be
pertain to removal and reinstallation in paragraph 3e.)
stored on storage racks. These racks will be made of
Some lithium sulfur dioxide batteries are unbalanced
loose, flat board; nails not being required. The uprights
and have been determined to be potential hazards
will be about 10 inches high and 12 inches wide. Shelf
whenever they undergo excessive current drain (as in
boards can be of any convenient size. The rack is
short circuits) or are unparalleled without dioxide
assembled with batteries sitting on the shelves and on
protection.
These batteries must be equipped or
either side of the uprights. The batteries must be close
packaged in such a manner as to prevent accidental
enough together to hold the upright rigid.
short circuit. Battery container shall be marked with
(1) Lead-acid batteries.
hazardous waste labels according to Federal and state
(a) Charged and wet. When received
requirements.
charged and wet, the cells are completely assembled,
(f) Handling precautions.
contain electrolyte, are fully charged, and ready for use.
1 Lithium
batteries
contain
The batteries will be stored in a fully charged condition
pressurized cells similar to aerosol cans. Any attempt to
and care must be exercised in handling. When stored in
disassemble, open, or mutilate them could result in
this manner, batteries must be kept fully charged either
injury or fatality.
by continuous application of a trickle charge or by a
periodic recharge once each month in temperatures
below 80 . When charging batteries, the vent caps
F
batteries may produce internal pressure at a rate in
will be kept in place to avoid electrolyte spray. Care will
excess of venting capacity which will cause the item to
be taken to assure that vent caps are functioning. It
explode.
should always be assumed that an explosive mixture of
3 Lithium batteries will never be
gases exists in and around charging batteries, unless
recharged. Such action may lead to venting, rupturing,
positive steps have been taken to eliminate them. For
or possibly a fire.
this reason, anything that could ignite these gases such
4 Keep batteries in original
as an open flame, a spark, or smoking should be
protective packing until ready to use or installation in
prohibited. Water will be added and specific gravity
equipment.
checked every week. Because equalizing charges are
5 When not in use, remove
given, generally, at 30-day intervals, the batteries will be
batteries from equipment. Equipment will not be turned-
stored in a readily accessible place.
As the
in or stored with batteries installed.
temperatures of the storage area or zone and the age of
6 Nonsupply activity users (who
the battery have a direct bearing on the frequency at
are responsible for removal) should be advised of
which equalizing charges must be given, the individual
handling and storage procedures for new and used
activity storing batteries will determine the schedule of
batteries.
equalizing charges.
7 Extreme care and proper
Batteries may be stored several months in this
protective equipment such as splash shield, mask,
manner and are available for use at any time. New
rubber gloves, and apron must be used when handling
batteries that have electrolyte in them and that have
leaking or damaged batteries.
been given their first charge on batteries that have been
in service and are not worn out must be stored in as cool
8 Additional special precautions
a location as possible, namely, between 60 . and 80
F
identified in the literature or instructions provided by the
. Wet charged batteries should not be stored directly
F
manufacturer must be complied with by all handlers.
on a concrete floor. Lead-acid batteries, depending on
9 Any person who detects a
the quantity and size, will be stored in racks or bins in an
noxious gas, such as sulfur dioxide, in an area where
upright position to prevent spillage or leakage of
batteries are stored should leave the area immediately
electrolyte.
and call the installation spill response team.
10 Smoking is prohibited in battery
storage areas.
5-69
|