If an Ultrasonic Motion Sensor (UMS) is installed near the CU, ensure that it does not cause an alarm to
be activated when a secure condition is desired. Create an alarm condition (by activating a nearby
sensor).  After expiration of the time delay period, the Monitor Cabinet should indicate an alarm
condition.
(3)
Remove cause of alarm, turn mode switch to TEST/RESET and then to SECURE. At the Monitor
Cabinet, go to the Status Monitor Module with alarm lights flashing and move reset switch to ACK and
then to RESET. Monitor Cabinet should indicate a secure condition.
(4)
Turn mode switch to ACCESS. Monitor Cabinet should indicate an access condition.
(5)
Remove ac power fuse F1 from CU power supply. AC POWER indicator lights on Monitor Cabinet
should change from on-steady to flashing, and the audible signal device should sound.
(6)
Move reset switch on Status Monitor to ACK. Indicator lights should go out and audible signal device
should be silenced.
(7)
Reinstall ac power fuse F1 in CU power supply. AC POWER indicator lights should flash and the
audible signal device should sound.
(8)
Move reset switch on Status Monitor Module to ACK. AC POWER indicator lights should change from
flashing to on steady and the audible signal device should be silenced.
(9)
Remove ac power fuse F2 from Monitor Cabinet power supply. Signal Module lights should change
from on-steady to flashing and the audible signal device should sound.
(10) Momentarily depress ACKNOWLEDGE switch. Signal Module lights should go out and the audible
signal device should be silenced.
(11) Reinstall ac power fuse F1 in Monitor Cabinet power supply. Signal Module lights should flash and the
audible signal device should sound.
(12) Momentarily depress ACKNOWLEDGE switch. Signal Module lights should change from flashing to on-
steady and the audible signal device should be silenced.