IAC Intelligent Access Controller (Cont.)
LK7-1
ON
IAC Input Address Bit 1
(IAC Input Address Shown = 13)
LK7-2
OFF
IAC Input Address Bit 2
LK7-3
ON
IAC Input Address Bit 4
LK7-4
ON
IAC Input Address Bit 8
LK7-5
OFF
IAC Input Address Bit 16
LK7-6
ON
Request-To-Exit Line Supervision, Enable (ON), Disable (Off)
LK7-7
ON
Door Contact Line Supervision, Enable (ON), Disable (Off)
LK7-8
ON
Alarm Inputs 1, 2, 3, 4 Line Supervision, Enable (ON), Disable (Off)
LK8-1
OFF
Dual Door Format Bit 1
(See Table Below)
LK8-2
OFF
Dual Door Format Bit 0
LK8-3
OFF
Unused
LK8-4
OFF
Unused
LK8-5
OFF
Unused
LK8-6
OFF
Multiple Site Type and Codes, Enable (ON), Disable (OFF)
LK8-7
OFF
Fall Back all Weigand Cards Selection, 32 Bit (ON), 24 Bit (OFF)
LK8-8
OFF
Multiple Card Swipes, Permitted (ON), Ignored (OFF) Removed)
LK9 1-2
ON(1)
Magstripe Reader, Enable (ON), Disable (OFF)
LK9 2-3
OFF
Weigand Reader, Enable (ON), Disable (OFF)
LK10 1-2
OFF(1)
Door 2Strike Relay (RL5, TB14) Normally Energized
LK10 2-3
ON
Door 2Strike Relay (RL5, TB14) Normally De-Energized
LK11 1-2
OFF(1)
Door 1Strike (RL3, TB12) Normally Energized (Fail Safe Mode)
LK11 2-3
ON
Door 1Strike (RL3, TB12) Normally De-Energized (Fail Secure)
LK12 1-2
OFF(1)
Aux/Alarm Relay (RL2, TB11) Normally Energized
LK12 2-3
ON
Aux/Alarm Relay (RL2, TB11) Normally De-Energized
Notes: (1) Mutually Exclusive Option Settings