Table 5-1. Troubleshooting Procedures - Continued
Trouble
Probable cause
Corrective Action
Monitor Module in swingout
rack and secure with screws. Se-
cure swingout rack. Turn on
switch S1 on power supply.
c.
Actuate ACKNOWLEDGE then
the RESET switch on Status
Monitor Module.
d.
If alarm condition is displayed,
Status Monitor Module is de-
fective.
e.
To remove Status Monitor Mod-
ule, unlock and open Monitor
Cabinet and turn off switch S1
on power supply. Release swing-
out rack. Remove screws that
secure Status Monitor Module
to rack and remove module
through front of rack.
f.
Remove jumper from terminal 4 of
input terminal strip. Replace
Status Monitor Module in swing-
out rack and secure with screws.
Secure swingout rack. Turn on
switch S1 on power supply.
g.
If a no-alarm condition is dis-
played, Status Monitor Module
is defective.
h.
To remove Status Monitor Module,
unlock and open Monitor Cabi-
net and turn off switch S1 on
power supply. Release swingout
rack. Remove screws that se-
cure Status Monitor Module to
rack and remove module
through front of rack. Install
new Status Monitor Module in
swingout rack and secure with
screws. Secure swingout rack.
Turn on switch S1 on power
supply. Actuate ACKNOW-
LEDGE switch on SMM.
5-9
|