Click here to make tpub.com your Home Page

Page Title: Table 5-1. Troubleshooting Procedures - Continued
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 5-6350-264-14&P-11
NAVELEX EE 181-AA-OMI-120/E121 C-7359-60-1
T.O. 31S9-2FSS9-1-11
Table 5-1. Troubleshooting Procedures - Continued
Trouble
Probable cause
Corrective Action
h.
To remove Status Monitor Module,
unlock and open Monitor Cab-
inet and turn off switch S1 on
power supply. Release swingout
rack. Remove screws that se-
cure Status Monitor Module to
rack and remove module
through front of rack.
i.
Install new Status Monitor Module
in swingout rack and secure
with screws. Secure swingout
rack. Turn on switch S1 on
power supply.
4.
Status Monitor
Defective Status Monitor
a.
Remove Status Monitor Module
Module does not
Module
from one-zone Monitor Cabinet.
correspond to ac
To remove Status Monitor
power condition at
Module, unlock and open Mon-
Control Unit.
itor Cabinet and turn off switch
S1 on power supply. Release
swingout rack. Remove screws
that secure Status Monitor Mod-
ule to rack and remove module
through front of rack.
b.
Connect jumper between terminals
3 and 4 of applicable Status
Monitor Module terminal board.
Replace Status Monitor Module
in swingout rack and secure
with screws. Secure swingout
rack. Turn on switch S1 on
power supply.
c.
Actuate ACKNOWLEDGE then
RESET switch on Status Mon-
itor Module.
d.
If AC POWER lights are lit, Status
Monitor Module is defective.
e.
To remove Status Monitor Module,
unlock and open Monitor Cabi-
net and turn off switch S1 on
power supply. Release swingout
5-7

Privacy Statement - Press Release - Copyright Information. - Contact Us