d. Transformer. The 500 KVA transformer is a Class 0A. It is liquid filled (oil), self-cooling with winding temperature
gage, liquid level and temperature gages and a pressure-vacuum gage. It has a wedge type tap changer for changing
the voltage ratio of a de-energized transformer, without breaking the transformer seal. The voltage ratings are 4160-
416Y / 240. 208Y/120. The transformer is directly connected to the high voltage input and low voltage output switchgear
cabinets. in weatherproof transition enclosures. (fig. 1-4 and 1.51.