Click here to make tpub.com your Home Page

Page Title: Table 5-1. Troubleshooting Procedures - Continued
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 5-6350-264-14&P-11
NAVELEX EE 181-AA-OMI-120/E121 C-7359-40-1
T.O. 31S9-2FSS9-1-11
Table 5-1. Troubleshooting Procedures - Continued
Trouble
Probable cause
Corrective Action
15. (Cont)
a.
(Cont)
located on back of Signal
module. Remove the
mounting screws and re-
move Signal Module.
(2)
To install new Signal Module,
position module in mount-
ing rack and install mount-
ing screws. Connect wires
to terminal board TB1.
Close and lock cabinet
door.
b.
Defective power
a.
Set multimeter to dc volts. Con-
supply.
nect meter leads to the fol-
lowing points in the power
supply. Meter should indi-
cate 20 vdc at each point.
Power
(+)
(-)
Supply
Lead
Lead
1 Zone
TB2-2
TB2-1
1 Zone
TB2-2
TB2-3
5 Zone
TB2-2
TB2-1
5 Zone
TB2-4
TB2-3
25 Zone
TB2-2
TB2-1
25 Zone
TB2-4
TB2-3
25 Zone
TB2-6
TB2-5
b.
If meter does not indicate 20 vdc
at each point, replace power
supply.
(1)
To remove one-zone Monitor
Cabinet power supply, un-
lock and open cabinet
door. Unlatch and swing
out mounting rack. Posi-
tion power switch S1 to
POWER OFF. Turn off ex-
ternal ac power by turning
off circuit breaker. Tag
and remove wires from ter-
minal board TB1, located
on back of Signal Module.
5-24